can anyone pls expain me about how can we design a cable
tray??suppose if have to draw a 3 nos of 50 sqmm AYFY and 2
nos of 35 SQmm of AYFY cable through the tray..how can we
design the tray size?? regards...
Answer Posted / 7anoter4
For open top solid bottom cable tray and without any
clearance between cables the cable carrying capacity
has to be reduced to 73%. However the tray width will be
only:
0.3*34+34+34+34+30+30+0.3*30=181.2 mm
3*50+ 117*.73= 85.4 A ; 3*35+ 96*.73=70 A
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the relation between reactive power and power factor for the what is the limit of reactive power and power factor
what is the difference between RMS & TRUE RMS VOLTAGE
What do you mean by a current transformer?
why constant voltage transformer should be start without load? and if started then what will happen?
What will happen if the voltage in my house drops from 220V to any lower voltage?
what is KA rating and how can we choose switchgears on applications
can a 150 kva 3 phase 440v/230V delta-wye step down transformer can be use as step up transfoermer with connected loads at 440v side?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
wht is embedded systems? what is new inthis field?
What is the formula to calculate the rating of a three phase air circuit breaker
Why need 3phase machine double earthing?
what is ramping rate of generator
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
why the carbon brushes are broken in srim while the motor runningtime
Mention the disadvantages of low power factor? How can it be improved?