can anyone pls expain me about how can we design a cable
tray??suppose if have to draw a 3 nos of 50 sqmm AYFY and 2
nos of 35 SQmm of AYFY cable through the tray..how can we
design the tray size?? regards...
Answer Posted / 7anoter4
You intend to run 3 cables of 3*50 mm^2 and 2 cables of
3*35 mm^2 type AYFY, I guess.
It depends on type and width of the cable trays. Let’s say
you want to use an open top and ventilated tray [ladder or
well perforated plate] and you want to carry the maximum
possible currents. Then, according to IEC 60364-5-52 Table
A.52-17 Note 2-you have to keep two cable diameters
clearance between cables and at least 0.3 time cable
overall diameter from the wall-both ends.
A 3*50+25 0.6/1 kV [according to IEC 60502-1] aluminum
conductor [compact], pvc insulated, steel tape armored and
pvc serving overall diameter 34 mm and for 3*35+16 overall
dia= 30 mm.
Here is the width calculation:
|0.3*34|O|2*34|O|2*34|O|2*34|o|2*30|o|0.3*30| where O =one
3*50+ cable diameter and o=one 3*35+ cable dia.
That means:
0.3*34+34+2*34+34+2*34+34+2*34+30+2*30+30+0.3*30=445.2
Then the tray width will be more than: 445.2 mm.
In 30 dgr.C air permissible current-carrying capacity will
be:
[See Table A.52-11 – Current-carrying capacity in amperes
system E aluminum]
[Or Tableau B.52-1 for aluminum col.7]
3*50 117 A
3*35 96 A
You may reduce the cable tray width but you have to reduce
the current in order to limit the conductor temperature to
70 dgr.C.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
defination of transistor controlled series capacitor
mention hazard experienced during installation
Please tell me the earthing procedures adopted for the STAR-STAR 3 Phase transformer in india and give a better sugession for earthing
what is the purpose of high speed earth switch in gas insulated substat
Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.
When a single pase capacitor run motor- run on 230vac and Case(1)run with 8 Mfd 250 vac.capacitor , Case( 2) run with 8 Mfd 400vac capacitor. What is difference between both case regarding power ,efficiency etc?
1. What is the exact formula for one weber? for example,(one ampere = one coulomb electron of electrons crossing a point of conductor at one second. i.e, 1A=1Q/1sec)
which metal is use in shunt
i have seen one 8.4 MW synchronous motor in a plant located in bellary it is fixed with brushless rotary rectifier ,anybody can explain its start up principle
From reading, Under voltage relay used also as phase sequence relay now, Why I use under voltage and phase sequence relay in the same circuit (ATS)?
WHICH SIZE A.B.CABLE IS USED FOR 11KV.
what is fault level of power system ?
what is the sludge current
What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)
In ACS 1000 drive we are using 12 pulse converter,why don't use 3 pulse converter.