what will be the effect if we increase the excitation of a
alternator??
Answer Posted / raul
If the excitation of an alternator is increased, then the
excitation voltage will increase, more flux in the air gap,
more rotor heating. But the excitation increase is governed
by the ROTOR HEATING LIMIT as per the generator capability
curve which over-rides the STATOR HEATING LIMIT. Above the
RHL, the automatic voltage regulator (AVR) takes over
control and starts reducing the excitation by Rotor current
limiter which acts in conjunction with the AVR.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Tell me all plants load factors i.e which plant operating on which load?
how to select proper cable for ct wiring so that drop within the limit.
What do you mean by dependent and independent voltage sources?
What is FM200 Gas??Applications........
where the lexical paramater will use in fron end?
Earth is a conductor or load?then ammeter connect to 3- phase supply,it shows the measurents or not?
Q: How to calculate Transformer losses , tell us by Formula.
What is the source of dependent source ?
What are the advantages & disadvantages of a group electrive drive?
design a LV scheme for a 15 storied building?
How to test the Secure Elite 440 Multi function meter working condition.
sir, Is their any measuring unit of knoking? please explian?
what is the maximum permissible limit value of leakage current and leakage counter reading to replace lightining arrester?
What is the difference between grid and off- grid system??
if there are six generators (3 gas CATT, one Jenbacher o1 MW each, and two nos Diesel 01 no 01 mw other 0.65mw EDGs ( say), 3 CAtt gas set have identical pole pitch,01mw EDG and Jenbacher gas Set have different pole pitch, how their power connection can be done to connect a common bus bar during installation. in short, how different pole pitched generators power connection can be done to connect a common busbar system through generators incomer ACBs.