how can we select the rating of Load break switch that is connected to
the primary protection of 200 kva 11kv/415v distribution transformer??
step by step calculated answr pls...thnk.u
Answer Posted / guna
Depends up on the load current we have to select the LBS
instead of VCB or SF6 (LBS is less cost for the same rating
when compared to the above cb's)
P=1.732*V*I
I = P/1.732*V
I = 200KVA/1.732*11KV
I = 10.49 A
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
and gate circuit diagram,amplifier circuit diagram
How is operate breaker failure scheme in substation
why current is constant on d.c?
i have seen one 8.4 MW synchronous motor in a plant located in bellary it is fixed with brushless rotary rectifier ,anybody can explain its start up principle
Explain the operation of grid connected central solar inverter ?
I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?
how much LT load can bear by the 100 KW HT connection.
how balanced in star delta connection ?
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
What is the Temperature to be set in Thermostat provided in Marshalling box of the Transformer / Motor.
a simple c++ program to calculate simple interst with its data members as private
sir, 3phase induction motor takes different pf and different KW in three phase while running,explain reason
What is the dependency of stiffness on load angle??
How does a transformer contribute towards the widespread popularity of ac system over dc?