Answer Posted / carl_ellis
Because it's a standard, widely used conventional pneumatic
control transmission range.
The 3-15 psi signal is a standard (ISA SP7) that came from
widespread use even before that standard came into being.
As early as the 1920's pneumatic regulators, pressure and
temperature controllers were using 15 psi at the high end.
Various low end 'live' or elevated zero values were used
before standardization.
Any pneumatic control or transmission signal starts with an
'elevated' or 'live' zero' at 3 psi because there is
internal friction and a fair amount of hysteresis in the
movement of pneumatic components, the flapper, nozzle,
diaphragms, spring preloads, pivots and bellows that make up
the transmitters and receivers. This friction and
hysteresis manifests as non-linearity below 3 psi. A 3 psi
minimum pressure puts the transmission signal into a linear
response range. Obviously, control system measurements,
signal transmission and the receivers need a linear response
to effect accurate and precise control.
Not all pneumatic control signals are in the 3-15 psi range.
The ISA SP7 standard (1996) that addresses instrument air
quality standards also lists 5-25 psi, 6-30 psi, 3-27 psi as
standard pneumatic transmission ranges, along with the
minimum supply pressure associated with each range. These
ranges all include an elevated zero.
Carl Ellis
Measure First
Is This Answer Correct ? | 22 Yes | 0 No |
Post New Answer View All Answers
if my flow is 20000 m3/h than which range of DPT i have to use????
how do calibrate the valves.. with clear manual
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
With N nodes and B branches what will have a network ???
List three types Level Gauges with their working principles
What is motion balance principle?
Pl send the model question paper of mahagenco account officer post
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
what step is taken for ESD ( emergency shut down) in DCS REPLY to hashimka20009@gmail.com
What is stripper & spilitter ? Diffrence in this.?
What is Erosion in a control valve?
when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??
What is voltage regulator?
Hi i am aneesh, done btech in applied electronics & instrumentatiin. And then i took mba in finance & marketing.After that i got placement in finance co and worked there for 3.5 yrs.Now i wanted to come back to engineering job.But without engg experience, i may not able to find an opening.i have done a course related to flow meters and ite calibrations. Kindly suggest where should i try to get a job?
can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?