Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

in my plant 100% feedwater control v/v is air to close but
due to instrument air fail,the valve opens but instead of
drum level high its get tripped in low low drum level.the
urv of level tx is 0 and lrv is -800.pls tell me the reason.
for such behaviour.

Answer Posted / carl_ellis

Air-to-close means that the valve fails open.

A boiler feedwater valve should 'fail open' so that the drum
level never drops too low, which can be an unsafe condition
and/or a damaging condition.

For that same reason, a boiler's feedwater valve should be
driven open on a low-low drum water alarm to prevent the
drum level from dropping too low and creating an unsafe
condition and/or a damaging condition.

Carl Ellis
Measure First

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

give me all the details about the interview and which type of question being asked

2227


I want to know about DDCMIS in detail ? please explain it. Also give name of reference books in which it is explained in detail in very simple manner.

3832


diff between neutral ,ground,phase , earthing and shielding?

2299


I need to know steps to Calibration Valve Guard......

1493


what is the difference between Cv and air consumption? why the customer needs Air consumption details?

1985


Explain PID controller tuning & any one method used for it.

7814


What is the use of single seated valve?

1077


What care will you take in the installation of control valves,SCADA,DCS and FOC in Oil and Gas Project?

2134


Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?

1528


How oil line flow measured?eplain about instruments used and working principle?

2063


There are many type of control cable like pair,core,tried, What are defination each one

2155


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

984


I want measure the volumetric flow of gas in waste heat recovery Boiler?Tell me how and which type of instruments required. Plz mail me:naba02222@gmail.com Sam please post the answer .

1973


send me HPCL paper

10315


how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.

2311