i am confusing about differential pressure transmitter as i
seen so many DPTs in different ranges how can we calculate
level and flow with mmh20 plz tel me
Answer Posted / carl_ellis
When the primary flow element (orifice plate, venturi,
averaging pitot tube) is sized to design conditions, the
result is a DP value corresponding to 100% flow rate. That
value is used to configure the DP transmitter.
For level, measurements are made from the transmitter datum
or installed position to the maximum level, with
compensation for the medium's specific gravity. When remote
seals are used, the specific gravity of the fill fluid is
accounted for in a compensating calculation.
Carl Ellis
Measure First
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
send me last 5 years questions asked in rrb chennai, for section engineer
Emergency Shutdown Systems/ Plant Shutdown System.
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?
why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
Please tell me details about Sox,Nox,SWAS analyser????
What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?
What is the reason PT speed not incresed in gas turbine?
How to calculate mmwc values into tonnes?
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
In apron feeder how TPH is calculated?
in differential pressure transmitter,min&max pressure range for hp&lp
applications of plc in printing and packaging?
what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?