On a 10 KVA UPS we have to provide a DC MCB for Battery bank
of 16 nos (12 V 65 AH).
What Shall be the current rating of DC MCB ?
Answer Posted / naveen kumar.b
Ans:- 60Amps MCB
how:-
for 16 battery net voltage is 192Vdc.
For battery low cut OFF voltage fixed in by all kind of ups is 10.5 each battery . so for 16 battery System battery low cut of votage is 168VDC
( :- at time low battery voltage only Dc current consumption is high, we need to take maximum current consumtion for select MCB)
total load we taken= 1oKVA Full load.
DC voltage at time low battery = 168
current consume (at time of low batter)= 10000KVA /168Vdc
current consumption is 60Amps arround
so 60Amps MCB is required
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What are the functions of different probes used in cro?
Why efficiency of generator is higher than motor at a particular load?
can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?
Yazaki india pvt ltd interview questions qurey related
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
What is the test block protection relay if any body know plz explained
what is basic difference betmeen normal & flame proof motor??
what kelvin's law ?
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
Is it required to use Automatic transfer Switch in L&T panel board if we use AMF panel with DG set? How the single line diagram will be? Please forward the material to sreenu_207@yahoo.co.in
what is load vs Torque curve & why it is used?
please send me previous year questions of jspl through which i could prepare myself for the test.
What are the disadvantages of hydropower?
How will you define capacitance?
what is difference between 9kv 5ka surge arrester and 9kv 10ka surge arrester.