Can we used Condensate Pot on flow transmitter which is
using on liquid having sluge and DP transmitter is in pit
and below the process line,Can we used Condensate pot for
accamulate the Sluge?
Answer Posted / carl_ellis
Yes, you can use a condensate pot to accumulate the sludge.
It's just a version of a "drip leg" that extends down
vertically below the tap or port for the impulse line (at
the datum elevation) to the DP transmitter. Other methods
are just constructing a drip leg from pipe fittings that are
rated for the temperature and pressure.
A consideration is whether the drip leg or pot can be
drained to remove the sludge, because it will fill up over time.
Carl Ellis
Measure First
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
What is modbus?
Explain the key components of control loop?
Explain the combusion chamber
What are different types of valves?
selection of the zener barrier for the hazardeous area zone 0
how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i
Explain bernoulli’s theorem. State its application.
hi i am eswar i want to know the instrumentation interview questations for eil(engineers india ltd) i have applied for engineer post in eil please help in this.my mail id eswar310@gmail.com
How to convert mmWc(mili meter water colam) to tph(ton per hour)?
How to calibrate the flow transmitter
What is the difference bitween control net scaner and device net scaner
How to calibration a control valve?
how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???
How an rtd work, and what volts/current goes to a rtd to measure the resistance?
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.