What is the harm if we install primary side 11 KV VCB at a
distance of one Km from the 11/3.3KV 12.5 MVA transformer
through 11 KV cable.
Answer Posted / darklord
No immediate harm ,but during maintenance this 11kv line
between VCB and transformer need to be discharged with out fail,
Also during switching action their would be switching surge
created due to oscillating of wave between vcb and
transformer which will heat and may damage insulation of
transformer.
Their would also be control voltage drop for 1000mtr wire
which will have significant effect on protection of transformer.
but proper control strategies will sort this problem
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is the pro & con of having 11kv & 33kv incoming, and what is the adv & disadv. of converting from 11kv to 33kv.
Where I can get the sample question for post of Junior engineer electrical-II For RRB Bhubaneswar.
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
What is the power factor of an alternator at no load?
What is installed in PAC that is control the humidity
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
what is parellel power factor correction?
What are different types of control systems?
which capacity of RCCB used for five thousand watt electricity load?
if we apply 1000ADC instead of 100ADC or We apply 50ADC instead of 100ADC,What will be happened in the test result value.Pl explain
In which working principal temperature transmitter work.explain in detailed.
Please elaborate th´evenin’s theorem?
why the pf of semiconductor device is improved the electrical devices
why we use sinosidal voltage / current instead of others in system?
What is the gross weight to copper ratio in slip ring induction motor of 4000 HP,6.6 kv, 372amp, 992 rpm GE motor.