Why consumers are charged based on Kwh basis why not on
Kvah basis.

Answer Posted / raj

Yeah... now industrial consumers are billed on KVAH only in Andhra Pradesh. Actually, this way of billing is the correct method to curtail low power factor problem in industries. In this case, we calculate the energy as below.
apparent energy,kvah = active power (kw)in each time block /power factor in each time block

Note : 1.presently the meters are designed for 15 minutes blocks.
2. In this billing method, the discoms dont penalize seperately for low power factor(as we already considered in thecalculation of apparent power.)
In the case of domestic, energy is billed for kwh only as it is uneconomical to place trivector meters ( as they consume less power and thier impact is very low on grid compared to industrial consumers )

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Best way to measure the Soil resistance of rocky soil, three probe method and four probe method

1444


what is difference between window type and wound type transformers?where we will use window type and wound type transformers?

1724


we have a rewind motor of 2Hp,2800Rpm, 220Volt AC. how can we choose the running capacitor for this motor, any formula for that?

1486


Define ohm’s law for a.c (alternating current)?

625


High speed earth switch operation with diagram

1882






defination of controlled shunt reactor

1787


how to calculate energy of 3-phase motor?

1551


how to calculate the magnetizing current of ct ( 800A/1A) for Relay 64

1039


My load is 1635 KW. & current pf is 0.884, I have to improve it for 0.99.Please suggest what KVAR value is needed?

1185


block diagram of 2 ups system connected in hot stand by mode?

7487


What are the material used for inductance coil?

693


What is meant by reverse polarity and how it can be fixed?

743


Why Stabilising Resistor used in REF circuit ?

2720


Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com

1428


how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.

1736