Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

HOW TO CALCULATE UPS BATTERY BACKUP TIME

Answer Posted / m.b.parthasarathy

The formula is as follows.

1. To find battery back up time : Battery AH X Battery volt X constant factor is divided by load(in watts). Perhaps if you have 100ah battery and the load is 500watts you can find back up time as follows.
EX: 1ooAH X 12V X 0.85 / 500
100AH X 10.2 / 500 = 2hrs.

2. To find battery AH : Back up time X load is divided by Battery volt X constant factor.Suppose you need 2hrs back up time with 500watts load, yu can calculate battery AH as follows.
EX: 2 X 500 / 12 X 0.85
1000 / 10.2
= 98.03AH. Commercially available 100AH battery only.

Is This Answer Correct ?    8 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

difference bewteen reverse current and alternating current

2291


Can we check ELCB constantly from R1 to R8 phase in 1 no DB?

1760


I HAVE A INCOMING 100A MCCB TPN 25KA, CABLE LENGHT OF 80M 70MM CABLE SIZE FROM MAIN SUBBOARD TO NEW DB.BASE ON THE FAULT LEVEL SETTING OF 45KA.I WOULD LIKE TO FIND OUT 25KA ENOUGH KA. APPRECIATE IF SOMEBODY CAN ASSIST ME WITH FORMULA FOR THIS. FRM: JEFF

4085


Difference of induction motor & servo motor ??

1868


why do we lay up the core of a cable?

2074


why we are using earth pit in sub stations.?

2227


What is the formula to calculate the no load current of a single & three phase induction motor

2336


11 kv input, 66 kv input advantages

1449


In EB metering we face problem kva jump even in no load condition.can any one help to control this

1889


How to calculate Grid rotor resistance(GRR) losses in slip ring induction motor?

4332


why dc is used in control circuits for MV & LV switchgeras instead of ac

2016


What are differences between Voltage, EMF & Potential difference ?

2069


How to calculate cable rating for 3 phase supply?

2248


if there is nutral in phase why we use earthing wire and grounding? even at fault condition the fault current flows to neutral (it is a lower path)

1884


A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is

1336