What is the calculating formula for HT and LT amps in a
transformer.
Answer Posted / raju kumar singh
Let suppose u have taken 1500 kva transformer of 11kv to 415 v u wanna be the current calculation for the both HT side and LT side. But u also think that u have connect load of the transformer 1000 kw. In this case both HT & LT SIDE power drawn is same. But this is three phase so we take formula
P equal to SQ ROOT 3 *V* I COS phai
Remember cos phai is necessary becuse of we know KVA :::: KW/ COS phai
U have connect 1000kw and its drawn full lo
ad then it wil be calculate in HT SIDE
1000*1000:::1.732*11000*0.8* I(u take power factor as0.8)
I::::65.6A
WHILE calculating in LT SIDE IT wil be
1000*1000::: 1.732*440*0.8* I
I:::1739.05A
because power drawn HT & LT SIDE depend on load connected to the transformer
| Is This Answer Correct ? | 32 Yes | 9 No |
Post New Answer View All Answers
What are the causes of having an rmu explode after installation? And how do u treat the bushings of an rmu?
How to set a Zone 1 distance relay for distribution feeder?
what is draiv work
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
What is the one main difference between ups & inverter ? And electrical engineering & electronics engineering ?
why booster transformer is used in sumpners test conducted on transformer????
What is Control & Relay Panel? And Remote Control Center?
What will happen if a dc source is given to a tubelight. Will it work or wont it work....
Why synchorised generators are used for the production of electricity?
explain different types of d.c motors?
What is mean by hot and cold loop testing?
how much flux density of CRNO core
i am electrical and elctronics engg passed out in 2009 want to attend for reliance placements.plz send me apttitude ,technical and hr question answers to my mail plz. my mail id-kat.bindas@gmail.com
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
how external lighting design? please give examples?