What is the calculating formula for HT and LT amps in a
transformer.
Answer Posted / raju kumar singh
Let suppose u have taken 1500 kva transformer of 11kv to 415 v u wanna be the current calculation for the both HT side and LT side. But u also think that u have connect load of the transformer 1000 kw. In this case both HT & LT SIDE power drawn is same. But this is three phase so we take formula
P equal to SQ ROOT 3 *V* I COS phai
Remember cos phai is necessary becuse of we know KVA :::: KW/ COS phai
U have connect 1000kw and its drawn full lo
ad then it wil be calculate in HT SIDE
1000*1000:::1.732*11000*0.8* I(u take power factor as0.8)
I::::65.6A
WHILE calculating in LT SIDE IT wil be
1000*1000::: 1.732*440*0.8* I
I:::1739.05A
because power drawn HT & LT SIDE depend on load connected to the transformer
| Is This Answer Correct ? | 32 Yes | 9 No |
Post New Answer View All Answers
What is the resistance of the field winding of a d.c. Shunt generator kept low?
how to calculate the distance relay faulty zone?pls explain?
What is the difference between solid grounding and impedance grounding?
what are the advantages and disadvantages of speed control of 3 phase induction motor by varying frequency explain with drawing
Why the arms of delta in a delta-wye power transmission system are kept constant??
Is RTCC panel needs any control supply.
we have 3.5MVA-11/6KV transformer. how can we calculate earth fault current and NGR calculation?
why ahould you show client/engineer activities clearly on the project plan
What is the purpose of using busbar mounting fuse?
Can we use both Electrical & mechanical interlock between tow breakers? if yes how, please explain
is it value of power factor is more than unit. whats effects in the source supply
What are steps to be taken while designing of DYN11 distribution transformer to achieve magnetising balance?
WHAT IS MEANT BY INSULATION CLEARANCE IN VACCUM?
Why corona leads to production of Ozone and glow of the color VOILET?
How does HT work & Voltage required?