1 Ton = ? amperes & power.
How much power 1.5 TON split AC consumes in an hour at 17
C , 26 C & 28 C (thermostat' temperature).
Answer Posted / abhijeet
Energy Efficiency Ratio for AC:
•EER = cooling capacity / Power consumption (both in Watt)
•EER of 1 TR (about 3,514 W) capacity air conditioner
consuming power 1,500 W = 3,514/1500 = 2.34
•Star Rating System based on EER - 1-Star: 2.5, 2-Star:
2.7, 3-Star: 2.9, 4-Star: 3.1 and 5-Star: 3.3……………………for
Split AC
 1 TR = 1500 W (Power Consumption- Including comp and fan
motor)
 1 TR = Thumb rule says it's 1.2kw to 1.5kw ..........
Depend on EER OR Star Rating
 1 TR = 3514 W (cooling capacity)
Hence approximate full load Current (I) is =
1500W /230V = 6.5 Amp ………for 1 Star Rating AC.
Is This Answer Correct ? | 38 Yes | 8 No |
Post New Answer View All Answers
can any one suggest paper presentation topies for electrical engg?
hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com
how to carried out DAR test in 11 KV Alternator ?
what is difference between 5A and 100A CT constructional wise and operation?
When we use 3 terminal resistor?
show the single line diagram of star delta starter with single phase preventer
Define reserve-generating capacity?
Factory acceptance test. FAT. For 132 kv transmisstion towers what is that meaning and what are the tests commonly companies perform now days.
how to calculate the fault in substation
What are the advantages of using distance protection schemes as opposed to normal overcurrent/ earth fault protection on high voltage feeders.
In our factory so many iron pillors are exists for supporting the shed/Hangar. If do more no of earthings at one piller instead of doing more earth pits in many locations and running earth strip around the hanger, I can save the money. Please suggest this method is acceptable as per Is specifications though the Earth resitance of the farthest piller is with in the limits as per IS specifications.
how do you test tachos and servos
why most of junction box vendors providing T5/T6 Temp class jb's for T3 area any special reason?
As per the Anchor capstan motor specification, full load current is 200A. starting current is 1750 A and acceleration time is less than 8 seconds. Please guide for selection of cable size.
what is consequences of neutral and earth connect?