Whether capacitor loads can be connected for testing a
diesel engine at its full load capacity? Is there any
limitation of capacotir load? Which is the best load for
testing DG sets?
Answer Posted / kj
Answer 1 is correct.
Normally a resistive load is used for testing a DG. As most
DG's are rated at 0.8 lagging power factor the resistive
load is calculated at unity power factor load on the DG.
This is usually 80% of the kva rating. This tests the
engine to full load.
Where it is required to test the generator at full load
also an induction load is used together with the resistive
load to give the correct power factor.
Capacitor loads are not normally used as DG's do not
operate safely on leading power factors.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are the types of windings according to the construction?
percetans
PLZ SEND ME SOME UNIQUE PROJECT OF ELECTRICAL ENG (B.TECH)
What is clock position of Transformer?what are the clock positions are there?and what is different of them?
how does high earth to neutral voltage affects electronic circuit?
how to protect motor in dol starter having capacity of 30 hp.40 hp?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
how many stairs have you climbed while you were coming
Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.
during installation time of transformer and alternator which points we have to observed?
Draw a SLD of HT distribution EB grid up to users Transformer?
list the type of vfd? wich is sutable for heating kiln?
What will be the diameter of pipe between conservation tank and transformer
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
what is efficient motors and how it is different from normal induction motors