why capacitor do not switch ON the DG power? (I had checked, capacitor ON in DG power that time current rating was reduced.)
Answer Posted / kj
Because it does not help the DG. The reduced current is
reactive only and does not load the engine.
If there is too much capacitance the DG can get a leading
power factor and if this is too great lose control of the
voltage.
In the grid capacitors are used to get the power factor
closer to unity and reduce the current. This means the
power lines can be smaller. If the power factor is leading
it is OK because others will have a lagging power factor to
balance it.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how to caculate cable size for diff types of loads? if anyone know the calculating procedure please tell me
primery try cell?
Is there any Institution for giving M-tech in Electrical engineering for those who r in service? Give the details please.
what is the criterion for selecting vector group of Transformers ? i mean how to decide vector group of Generator transformer, substation trasformer and transformer at consumer end
why we use condenser in the thermal power plant, althrough the same vapour will be again heated
what is metering cum synchronizing panel and how it is used?
When MICC cables used ?
How do we calculate over and under frequency tolerance from generator data?
When and where resistance earthing is used ? How to calculate the time constant for earth fault
what are the advantages and disadvantages of speed control of 3 phase induction motor by varying frequency explain with drawing
what is the best method of grounding in 30 MW generator?
whats the application of voltage regulation? and whats the voltage regulation's device?
What technology is used in latest generators?
What are the functions of temperature scanner in power transformer?
which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?