Why capacitor bank does not require in DG Set?
Answer Posted / kj
In a single DG the power factor is not a function of the
DG. It is a function of the load. Inductive loads will
produce a lagging power factor and capacitive loads will
produce a leading power factor.
If a capacitor bank is used and the PF on the DG becomes
too far leading the fact that the voltage rise leads the
current rise in the waveform causes induced currents to
flow in the rotor field. This induced current replaces the
current produced by the AVR. As the PF becomes more leading
the AVR does not produce voltage and control of the voltage
is lost. The voltage will rise above the nominal settings
if the PF becomes more leading after the AVR has shut down.
So although it is not normal practice to use capacity banks
with DG's, they can be used as long as the PF remains
lagging.
Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
what will happen if multimeter(selector switch at DC voltage) and terminal at current is connected to DC supply?
What is Primary And Secondary Injection Test of Relay and Other Electrical Devices. How IT is carried out.
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
what do you mean by class PS CT and what are technical details needed for calculating it?
how freewheeling diode improves the powerfactor
being an electrical engineer why you wanna come into software i have an very good academics what answer i have to give
What are the disadvantages of hydropower?
please give me all the Alarm .Trip ,Safety Relays & Conditions of UPS Systems mail me on ashokbabunhce@gmail.com
what kn of disc is used in 33kv,132kv,220kv,400kv,800kv transmission line
what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network
1)we have 1000 cfm Blower,Dia-1Mtr,Velocity of air 94 m/s 2)We have Natural Air velocity 94m/s 3If i Put Wind Mill in natural air ,speed is 94m/s Then it will generate Assume 100kw 4)If i put same wind mill across the Blower,air speed is same 94m/s now the Question is Will it generate 100 kw?
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
does the Trivector Meter of three phase automatically takes care of the low power factor and gives the reading accordigly or it does not take care of the Power factor while giving the readings please explain
could you measure current in parallel?
how to minimize earth resistance upto 2Ω, if the resistance is 6 Ω ?