Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why we choose 400kv,220kv,132kv,66kv,33kv transmission
voltages for transmitting power. Why not other voltage
levels.

Answer Posted / prakash krishnappa

Hello

There is no rule to select in multiples of 11kV.
Way back in 1887, when the 1st AC transmission was made in
England, the sending end power station was designed for
10kV. At the receiving end, they witnessed close to 11kV
due to ferranti effect ( named of Engineer Sebastian Ziani
de Ferranti who designed the power station). This lead to
finding out the effect of capacitance on lightly or no load
overhead line on the receiving end voltage. Engineers then
started designing equipment for 11kV and perfected the
egineering design for a max of 12kV for 11kV system. This
is how 11kV was made as starting point. There after, the
Engineers started designing in multiples of 11kV ( no
particular rule though !). In US, you can see 7.5kV,
14.4kV, 161kV, 230kV , 345kV etc which are no where near
multiples of 11kV. Since English people were more daring
and liked travlling for business all over the world, they
took this 11kV( and its multiples) around the world and few
countries like US and some European countries did not take
this 11kV or multiples of 11kV.

Is This Answer Correct ?    8 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the high series capacitance winding on high voltage power transformer ?

2212


how we control automatic generator i'e with to supply (main supply and local generator) when the main supply was break to supply the local supply automatically to begin supplying power.I now this control circuit is the combination of contactor time delay contactor switch and overload relay .but my question is how we combine those component thank you

2045


i am gng to visa interview this july i have 4 backlogs gre 1010,toefl 75,pls give me the tips pls pls

2212


write a program that prints prime numbers from 1-20 in digonal form

2062


What is the unit of charge and current?

1208


What is bode plot?

1313


Draw transformer phasor diagram.(full load,no load)

4223


What are the differences between single phase and three phase?

2099


WHY IS THE EARTH FAULT CURRENT ALWAYS LESS THAN THE NORMAL CURRENT??

2281


What are the temperature elements?

1301


if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please

2135


I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400

1864


how much GROUND & NEUTRAL VOLT maintain in data center.

2115


Explain how you intend to work under pressure to meet up with deadline target?

5270


What are the criteria shall be considers for sizing Fuse and MCB? If the rated current is 10Amps what should be the fuse size / MCB Size?

1706