why there is a fault occurs, if a phase wire touches ground..
and the fault not occurs when we connect a bulb between phase
and ground..??
Answer Posted / 7anoter4
Let's say the cable supplying the outlet [phase-neutral-
ground] is 3*14 awg copper and the length up to supply
panel is 300 ft. The conductor resistance is about 1 ohm[at
rated temperature].For 120 V voltage supply at panel if the
phase contact the grounding conductor the current will be
120/2=60 A. A 15A fuse will burn in less than 1 sec.
However, usually the short circuit current is 500-1000A.
If a bulb is connected between phase and ground ,for a 100
w bulb 120 V the resistance will be 120*120/100=144 ohm.
The current will be 120/144=0.83 A.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
from which formula we select a capacitor rating?
Dear sir, I have completed DECE in the year 1995. I have work experience in HT and LT LINE more than five years. Now i am doing BE in EEE from rajasthan university. After completion of BE,can i apply "C" Licence sir? Please reply.
size of condotory fron voltage level
Why arc quenching is used in Diode ?
I need model question papers for RRB section engineer Chennai... Please send to my E-mail Id:- maitheerainbow@gmail.com
What is load boxes ?
What is the maximum number of swithes that can be connected in series up to down stream point in an LV Distribution system?
how is control wiring coding is done in a CRP panel ?
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
What is a differential amplifier? Also, explain cmrr.
what is the purpose that we use PLC system in power system
do you have some of interview Questions in power and genrator section in general whith answers
we are having 110 Kv,250mA Electrostatic precipitators for coal fired boilers. what will be static voltage and current after discharge and what time it will remain before earthing?
HOW can i REuse the fused MLL LAMPS & GLS LAMPS at our factory
Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.