Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why there is a fault occurs, if a phase wire touches ground..
and the fault not occurs when we connect a bulb between phase
and ground..??

Answer Posted / 7anoter4

Let's say the cable supplying the outlet [phase-neutral-
ground] is 3*14 awg copper and the length up to supply
panel is 300 ft. The conductor resistance is about 1 ohm[at
rated temperature].For 120 V voltage supply at panel if the
phase contact the grounding conductor the current will be
120/2=60 A. A 15A fuse will burn in less than 1 sec.
However, usually the short circuit current is 500-1000A.
If a bulb is connected between phase and ground ,for a 100
w bulb 120 V the resistance will be 120*120/100=144 ohm.
The current will be 120/144=0.83 A.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what are types of encoder

1856


What is an alternator impedance value?

2841


When distance between two pulleys is not fixed, the tension of belt is adjusted by a) driver shaft b) driven shaft c) adjustment screw d) belt

3012


What do you mean by phasors?

1058


100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.

2347


how braking & making capacity of circuit breaker is calculated?

1987


why to use freewheeling diode ( diode in revers bias mode) across dc coil

4988


A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .

2624


For overhead protection we use which transformer?

2470


how the works electronic energy meter?

2151


Can Anyone Answer anyone of these ? Q1) why direct SOLUTION of Load Flow Studies in Not Possile ? Q2)Why majority of Buses in power system are load buses Q3)Why one of the buses in Power system is taken as reference bus (slack or swing) Bus ? Q4)Bus Admittance Matrix is a sparce (means it contains some zero elements ) matrix , give reason

1900


What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning

1981


how to select energy meter? have any calculation?

2987


I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.

1943


why are installed water leakage detection system data centers & server rooms

2370