Why there is no provision of breaker in between primary of UAT and generator
Answer Posted / 7anoter4
I think, it does not need a UAT breaker since if the UAT
does not supply power to the generator auxiliary the
generator will shut down, any way. So, the generator
breaker will protect the UAT also. Providing a UAT breaker-
not taking into consideration the expenses-it could be an
other generator failure point if this breaker would fail or
would open unmotivated.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the permissible maximum flux density in transformer core?
If I want to buy a new Xformer for my plant what are the main parameter will I need to check?
how much LT load can bear by the 100 KW HT connection.
sugest any typical project ?
Why Ac Systems Are Preferred Over Dc Systems?
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
Explain the operation carried out in thermal power stations?
What is the difference between multimeter
how to find the resistance and gap volatage of the diode??
how is find out kwh step by step
State uses of different types of stsrters with different capacities of motors as below: a. up to 5HP b. above 5hp to 10hp c. above 10hp to 20hp d. above 20hp
Explain the laying procedure and laying depth of submarine/subsea power cable for 220/400KV system? Also available cable diameter?
diff.between servo motor and ac motor
During Starter Panel Com missing I Found The Main Incomer 40Amp MCB 10KA Trip When Motor Change Star To Delta Motor Rating 20HP BUT When We Use Same MCB To Other Motor It Does Not trip Or What Is Necessaries for Star Delta Starter MCB SFU MPCB OR MCCB And What are The Breaking Capacity of MCCB in the Motor above 15HP