What is the Difference Between MCCB & ACB & VCB
Answer Posted / guy
All are breakers
MCB=Miniature CB MCCB=Moulded Case CB ACB=Air CB VCB=Vaccum CB
ELCB=Earth leakage CB RCCB=Residual current CB
Basically a CB is a switch which automatically opens in case of fault (many different faults exist)
The acronyms MCB, MCCB, ACB, VCB are referring to the technology used (i.e. how the breaker is manufactured)
As many others said before me arc breaking technology is different.
MCCB or ACB?
When choosing a breaker at design stage you look at the breaking capacity (kA), the rating, the functionalities of the trip unit (short, long, instantaneous protections, electronic type? yes or no, themal? magnetic? need earth protections? ) The selectivity with others breakers in the network, etc.. This will bring you to choose a ACB or MCCB, the one who will meet your design criterias.
If you want a 400V 5000A for sure no MCCB will be available but ACB will be
For a 1000A both will be.
Note that in some others languages than English there is no difference between MCCB and ACB.
VCB are common on HV (high voltage) but this is wrong wording as well because for instance Schneider VCB use a gas (SF6) and not vacuum.
So take care of the words that are mainly use for commercial purpose.
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
How can we find the breaking capacity of a Load breaker switch (LBS) fed from 11 kv supply??ex:50KA, 26kA etc???detailed step vice answer pls.
what are symmetrical and non symmetrical components in electrical installation.
do you have some of interview Questions in power and genrator section in general whith answers
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
What is evaporator & condencer & compressor
what is the difference between megger and earth resister ??
What is the safety of UPS?
how freewheeling diode improves the powerfactor
Why are iron cores in transformers made laminated?
What is the rate of WCT on the Electrical Contracts comprising of DG Sets and Civil Works in Delhi ?
We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.
how did the testing of protection relays done through current injection
What was your role in the silicon evaluation/product ramp? What tools did you use?
Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?
i am completed diploma in ece,and working in ht and lt lines.so is elligible diploma in ece for get electrical C Licence?plse give ur opinion?