how we can calculate the transformer size.
Answer Posted / satya mahesh
load factor(LF) and utilization factor(UF) will play a
major role in transformer selection.
Connected load-4810
Maximum demand in a month-1582 Amps
Average load which will be the average of running loads
came in a month-1173 Amps
LF=average load/max demand
=1173/1582
=0.74
UF=No.of hours running Equip/total hours in a month
=(30*20)/(30*24)
=600/720
=0.83
Transformer size= Connected load X LF X UF
=4810 X 0.74 X 0.83
=2954 Amps
for 2954 Amps 2500 KVA(3484 Amps) transformer was suitable
in continution to the future loads also.
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
Why did lightening arrestor solid copper rod head is sharp on mobile tower top?
what is method for testing CT
Explain the term parallel path in dc machin ?
how is capacitor bank look like
why the NGR (neutral grounding resistor) always OFF during DG off?
I want to ask that is there any relation between current denesity of copper and material purity. also is ther any standard which defines the standard current denesity of material.
What is the difference between the impedance percent and impedance voltage ?
How to measure size of cable on a given load
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
WHAT R THE SAFETIES IN A HIGH TENSION PANEL N LOW TENSION PANEL. ALSO WAT SAFETIES R THERE IN A 200 KVA TRANSFORMER?
Why are lt windings placed near the core?
Explain the operation principle, advantages and disadvantages of the following converters: a) A 12 pulse converter b) A Switch-mode inverter c) A thyristor inverter
SIR, GIVE ME OPGW SAG CALCULATION FORMULA I AM DAE ELECTRICAL. THANKS
Swg formulae
What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?