how much capacity(rating) of generator required to operate a
load of 100kv.
Answer Posted / abhishek jha
rating depends on wattage rating and not on volts. also if
it is 100 kw then if its power factor is assumed to be 0.8
then to supply that load ganerator rating should be
100/.8=125