how is a displacer type level transmitter calibrated.explain the method?

Answer Posted / haridass kwt

To calibrate the displacer type LTs by fixed in the w/bench,

First remove the head, clean displacer and chamber and
assemble,

fix the calibration setup (drain isolation, clear tube and
marked scale),

Calculate 100% position of fluid filling, by the Sp.
gravity of the fluid where the LT being used. (Ex: If sp.gr
is 0.8, then the 80% of the displacer height to be marked
in chamber due to the water used for calibration), and mark
every 25% in chamber ouside for reference.

Fill the water and check the transmitter/board/sensor
response approximately.

Fill the water till the displacer touches. and chk 0% and
adjust to 4mA.

Fill the water till 100% to check span and adjust 20mA.

(If the LT s not responding, replace LVDT/board and chk)

Repeat zero and span check 4-5 times and the chk every 25 %
rising and falling.

If ok, the prepare the calibration report and tag it.

Is This Answer Correct ?    11 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can we test a bently nevda 3500/42M accelerometer monitor card by simulating it with test equipment?. what king od of signal (milli volts or volts or or resistance ) we should feed in the terminals of the card?

2005


I WANT SECURITY PAPER MILL, HOSHANGABAD TEST PAPER.KINDLY SEND TO MY MAIL ID

2291


please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com

1234


I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.

1885


what is scale factor of proximitor & unit of the vibration.

1679






TEMPERATURE VARIATION FOR FREQUENTLY.

1512


i am preparing for BARC ,so plz mail me how to prepare for BARC. ALSO IF POSIBLE SOME RELATED QUESTIONS. MY MAIL ID IS khushi_4uall2003@yahoo.co.in

2552


Q1: Consider part of a control loop, which excludes the transmitter, consisting of a process, a controller and a control valve which may be represented by two dead times of 0.5 min each and three exponential lags of 0.8 min., 1.0 min. and 1.5 min. respectively. We wish to express this system as an overall first order plus dead time (FOPLD) model ie gain, time constant and process dead time. (We will see later that this is often done, to simplify controller tuning). For this exercise, gain is considered to be 1.0. (A) If the transmitter is a flow transmitter whose behaviour can be described by a dead time of 0.2 min. and an exponential lag of 0.5 min. in terms of the overall dead time and overall first order lag how can the system behaviour be approximated ? Overall dead time = Overall time constant = (B) If the transmitter is a temperature transmitter with a temperature sensor in a protecting well whose behaviour can be described by a dead time of 0.7 min. and an exponential lag of 15 min. how can the overall system behaviour be approximated now? Overall dead time = Overall time constant =

1442


why we r opening HOT BYPASS valve during startup of a compressor?

1594


in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.

1576


What is the difference between uv and ir scanners? and what is the workig principle of both

1940


What is 3 element control system

1012


There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?

1450


Why mixer nd grinder Is example of constant torque load not variable torque load ???

1492


How to Calibrate Level Switch in field

788