how is a displacer type level transmitter calibrated.explain the method?
Answer Posted / haridass kwt
To calibrate the displacer type LTs by fixed in the w/bench,
First remove the head, clean displacer and chamber and
assemble,
fix the calibration setup (drain isolation, clear tube and
marked scale),
Calculate 100% position of fluid filling, by the Sp.
gravity of the fluid where the LT being used. (Ex: If sp.gr
is 0.8, then the 80% of the displacer height to be marked
in chamber due to the water used for calibration), and mark
every 25% in chamber ouside for reference.
Fill the water and check the transmitter/board/sensor
response approximately.
Fill the water till the displacer touches. and chk 0% and
adjust to 4mA.
Fill the water till 100% to check span and adjust 20mA.
(If the LT s not responding, replace LVDT/board and chk)
Repeat zero and span check 4-5 times and the chk every 25 %
rising and falling.
If ok, the prepare the calibration report and tag it.
| Is This Answer Correct ? | 11 Yes | 1 No |
Post New Answer View All Answers
what are the selections available in configuring a burnout protection of a controller? thanks
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?
what is a good line as ic engineer as maintenance ,oc, project, calibration ,validation engineer?
hello friends, can you please send me the model paper or question paper to be prepared for hpcl examinations????????? You can mail me at rahim_here@yahoo.com waiting for your reply........... help me .. plz.....
What is the working principle of the magnetic meter?
What inherent design and operating principles are included in a modern control system to use predictive maintenance practices to increase overall system reliability?
what is performance test.need defination
How is PH sensor works ?
how to change measuring units from mmwc to cubm/h in rosemount air flow transmitter with hart communicator fluke 744
Why do you want to work here
Define cryogenic?
what is cold loop? difference between hot and cold loop?
why we take %i0.0 as input for twido plc
What is the meaning of wet leg
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.