if i conncet ct with ct ratio of 600/5 to an energy meter
having ct ratio of 100/5, the reading show by the meter
will correct, if wrong is there any method to calculate
correct value with shown value, if yes please state
it.....
Answer Posted / wareagle
If the meter is designed to use a 100/5 ct, it will receive
5 amps when the load is 100 amps. If the ct were a 600/5,
the meter would receive only 1/6 x 5 amps or 0.83 amps
which would be a low reading. You would need to multiply
the reading by 6 to get the correct value. You would likely
not get the the exact reading with the 600/5.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
please give me solution to rectify the emi(electromagnetic interference)
What is the size of a 60 watt and 80 watt tubelight?
What kind of maintenance is conducted for Transformer
Dear sir, By which formula u can calculate for a particular kv line there is a range of mw.
we have two generators different capacity on 15 MW and other 6MW at 11 KV , 15 MW gen. bus short level current 40KA,and 6MW short level current 25KA,, length of cable 100MTR between 6 MW from 15MW gen. for bus coupling . kindly tell any one can we use both NGR OR one NGR from any GEN. BOTH NGR has diff. rating. Tariq pakistan
What is the lockout relay
Merits & Demarits of Oil circuit & Air circuit breakers ?
What will happen if i replace a inductive proximity switch with photo sensor in a machine?
How to measure size of cable on a given load
why the protection turbo generators is most complex?
i have 500 amp inductive load of motors ,,,pleas tell me how can i calculate for capacitor bank for improving my power factor to 99 .....calcullations for capacitor bank,,,,
We are designer please help me calculate the size of 11kv cables from step up transformer to M.V panel, total load is 5 mega watt distance 900 feet (used aluminum type cables) please provided formula for calculate the cable with example.
How to choose the vector group for the step up and step down transformers??? Tell me the which vector group is suitable for step up and step down transformers and whats the reason to choose and whats the benefits???
What is nichols chart?
If mutual flux is 1.2wb & power factor is 0.8 lag , then what is the Useful flux of a transformer?