why we use post insulators in no ofstacks at substation for
supporting equipment ? why we not use single post insulator
Answer Posted / rahul singh
In order to increase its creepage distance so that
recommended phase to ground clearance can be attained. Also
the helical shape/edges are provided in stacks to avoid the
accumulation of water in case of rainfall & mechanical
strength also increases in this design.
For 220kv Post Insultors - Creepage distance= 6125mm
For 132kv Post Insulators- Creepage distance= 3625mm
For 33kv Post Insulators- Creepage distance= 900mm
Thank you.
Rahul Singh
Electrical Engineer
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Dear Sir I am living in Jaipur Rajasthan now I did complete my b tech degree in electrical engineering in 2012 Sir how I gate certificate of competency for electrical supervisor
Did RMU have ct and pt ?
how to test power transformer.YNd11
how solar power plant energy meter multiplication factor
how to apply b license to c license in tneb
List advantges of active filter over passive filter?
What is the difference between single core 2 wire and single core 3 wire system? Which application we are using this? and for What purpose we are using this?
What is meant by cold loop test in instrument
What should be the Sandwitch type Al. bus bar capacity for 2 M.W.Gen. set, having continuous full load current- 3463 Amps,ambient temp.- 50 Deg. C., Required temp. raise-20 deg.C., it will run 24 hrs, 365 days on full load, required highly reliable.
what is the max. acceptable leakage current in 33kv bus bar
pls tell what are doing the three phase motor star and delta connetion with circuit diagram and control wiring .
how the characterstics of control valve being done
I need the recommended size for a 3 phase transformer at 13.8 KV Primary and connected loads of 3000 kVA at 4200 volts and 2375 kVA @ 480 volts AC.
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases flux A does not alter B decreases C increases D none of above
how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.