Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

My flow transmitter range is 0-1000mmwc.DCS range is 0-
100m3/hr.What is correspond out put in terms of milliamps
if my flow is 65m3/hr

Answer Posted / krishnakumar k

flow meter range 0-100m3/hr will give output 4-20ma

for 65m3/hr output is = {(16/100)*65} + 4
=14.4ma

Is This Answer Correct ?    18 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can any send me a forbes marshall dtron 316 manual

1897


what is the input of digital counter during the the calibration time?

2263


How to Calibrate Ultrasonic Level Transmitter in field

1292


How to Calibrate Vortex Flow transmitter in field

1205


what is the criteria to decide conductor size of a cable ?

1814


How to Calibrate Level Troll in field

1334


I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.

1501


Please tell me details about Sox,Nox,SWAS analyser????

3670


I have energy meter for educational project having 0.5s class but my friend need 0.2s class meter , which one is good for that purpose and what is the actual difference of that two classes , need very easy example also.??

1362


all questions related to instrument technician in any offshore oil and gas company.

21614


how u choose thermowell lenght n pnumatic C/v size?

2048


What is the GK Value in Flowmeter?

3632


when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??

2127


Specific gravity.

1818


Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?

2192