what is ZERO SUPPRESION and ZERO ELEVATION?
Answer Posted / rizwan afzal
Suppression.If transmitter is installed in such
configuration that positive pressure is acting on the HP
side even when level in tank is zero. Such as Tx is
installed below datum point then head pressure of impulse
line is always acting on the HP side of the Tx even if tank
is empty, to componsate that head pressure a -ve biasing is
applied which is equal to the head pressure.
IN OTHER WORDS the LRV of Tx is kept at +ve pressure(equal
to head pressure causing error), so that Tx should give 4mA
at that head pressure.
Elevation.If transmitter is installed in such configuration
that positive pressure is acting on the LP side(DP is in -
ve value when level in tank is zero). Such as Tx is
installed in wet leg configuration then head pressure of
wet leg is always acting on the LP side of the Tx (even if
tank is empty), to componsate that head pressure a +ve
biasing is applied.
IN OTHER WORDS the LRV of Tx is kept at -ve pressure(equal
to head pressure causing error), so that Tx should give 4mA
at that head pressure.
Or to keep range in +ve, Tx can be installed in such manner
that LP side is connected with datum point and HP side with
Wet leg.
| Is This Answer Correct ? | 23 Yes | 0 No |
Post New Answer View All Answers
What are different type of instrument cable
A DP transmitter is used to measure the level of an open tank. The drain line of the tank is connected to a control valve, and is configured as, if the level of the tank is 90% the valve should get open 10%. And if the tank level is 10%, the valve should get open 90%. Draw wiring diagram and explain how to configure DP transmitter and control valve using HART communicator. If the span error at output is 1%, what will be the %opening of the control valve at 60% level of the tank?
how to calculate the total flow in square root
What is the start up procedure of desalter
how to measure draft pressure in transmitter pl. give its single line digram
Conversions
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
Why do you want to work here
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
Linear amplifier.
how to calibrate 0- 150 psi presure gauge by dead weght tester
what is compensation? temprature & pressure
How can test or measure the probe and extension cable to identify if the problem at the probe or cable or at the driver it self? (pleast notify the measuring method)
NSV type probe stands for
what is output of FOUNDATION FIELD BUS transmitter