how much current will be drawn by 3 phase, 415v, 50 hz, 20
ton central ac
Answer Posted / saad
one ton = 1250 watts
20 * 1250 = 25KW
P = 1.732 * V *I * Caso
25000=1.732*415*I*0.8
I=43.47Amps
| Is This Answer Correct ? | 4 Yes | 3 No |
Post New Answer View All Answers
Which motor will you choose which can operate in both lagging as well as leading power factors?
for a 400kv t/m line with 10 ampere current will corona occur?
why sometime we get electrical shock while touching the ballon of dish tv connection ? which we should not get.
what is the minimum clearance between a 11KV 150KVAR capacitor cell and series reactor.can a series reactor can be mounted in the same structure of the capacitor cells structure
IF DISTANCE IS 100METERS B/W AMP.METER AND CURRENT TRANSFORMER WHAT WILL BE AFFECT IN ACCURACY .METER CAN SHOWING ACCURATE CURRENT OR NOT IF NOT WHAT CAN I DO TO GET 100% ACCURACY.
advantage of motor design on higher power factor . normally motors are designed for .8 power factor. what is advantage of designing at .88 power factor
How to work definite,over pluxing,revers power,OSR relay
how is the magnetic current test is different in delta-star and delta delta transformer.
Can you explain about TEE protection scheme?
What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.
Please tell me the earthing procedures adopted for the STAR-STAR 3 Phase transformer in india and give a better sugession for earthing
The D.C. spark test is applicable to single conductor cable & assemblies of insulated single conductor cables without insulation shield,metallic sheath or metalic armor?
I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?
would the same effect be achieved by reversing the connection to one winding of the induction motor 3-phase?
Explain difference between stand by earth fault and residual earth fault protection?