What is basic difference between Soft Starters And VFD
drives?
Answer Posted / dikesh patel
we are using soft starter ofallen bradely flex model for
180 kw hall screw motor configuration of s s is in delta
mode i always observer the starting kick around 9oo amp flc
of motor is 180 amp how soft starter is not limiting its
starting current up to 400/500 amp it is almost about the
stardelta kick then how we can say that soft starter is
meant for limiting starting current kick
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
why constant voltage transformer should be start without load? and if started then what will happen?
I want to know all basics of electrical engineering
what is the difference between pvc & fiber glass cables
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
What is thresh hold value of current?
What is meant by Load Encroachment in OHL Feeder Protection?
i need the curve duty cycle and amper for (150 kva @50% dyty cycle) transformer turn ratio :19 and vin 400
i am trying to PSUs/govermeant jobs since last 2 years but still i m not success, plz help me.
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
i have applied for junior engineer 2 c&w for Guwahati RRB please send me last five year question paper
10 Mtr Hight of Lighting Arrestar how much area coverd??
when ID fan will immediately stop through VFD what exactly cause and problem the ID fan
What are the types of windings according to the construction?
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
What is a dc motor?