Answer Posted / warren holden
Yes, a control valve can be used without a positioner.
Some of the previous responses contain correct information
about certain elements of what a positioner actually does
however they do not address the fundamental issue from a
control perspective.
The positioner on control valve is essentially a cascade
(inner) loop acting as a high gain proportional controller
within the external (outer or master) loop (Shinskey, G.F.
1988). The positioner will be beneficial if its response
time constant is faster than the master loop element(s)
i.e. in the case of a temperature control (master) loop the
control valve positioner dynamics will undoubtedly be
faster than the temperature measurement change dynamics
(this being a fundamental requirement of cascade control).
However, the control valve positioner is of no use, and
actually a hindrance, on fast acting master loops i.e. flow
control with fast change dynamics. Hence control valve
positioners are often not used on flow control loops where
the outer (master) loop flow measurement and associated
controller can handle the control valve positioning quite
well themselves.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
For what reason would you possibly be compelled to make use of a Smith Predictor. Explain the idea behind the operation of this device.
types of cable..? Use of every types of cable..?
why direct mounted pressure transmitters is always installed with DBB ( double bleed block) valve in process line or top of the tanks ?
Draw symbols of the following :
give some question relative instrument fitter?
CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?
What is sensitivity in vibration probes..?
how to turbine speed measurement?
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
What is the difference between mmwc and mmwg?
What is the use of double seated valve?
what is the usage of QDV & VOLUME BOOSTER
How is automatic reference junction compensation carried out in temperature recorders?
Valve positioner and actuators in detail.
Please tell me details about Sox,Nox,SWAS analyser????