can we use a control valve without positioner

Answer Posted / warren holden

Yes, a control valve can be used without a positioner.
Some of the previous responses contain correct information
about certain elements of what a positioner actually does
however they do not address the fundamental issue from a
control perspective.
The positioner on control valve is essentially a cascade
(inner) loop acting as a high gain proportional controller
within the external (outer or master) loop (Shinskey, G.F.
1988). The positioner will be beneficial if its response
time constant is faster than the master loop element(s)
i.e. in the case of a temperature control (master) loop the
control valve positioner dynamics will undoubtedly be
faster than the temperature measurement change dynamics
(this being a fundamental requirement of cascade control).
However, the control valve positioner is of no use, and
actually a hindrance, on fast acting master loops i.e. flow
control with fast change dynamics. Hence control valve
positioners are often not used on flow control loops where
the outer (master) loop flow measurement and associated
controller can handle the control valve positioning quite
well themselves.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what are the diff. in servo and regulatory control?

3474


how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i

845


In turbine what does term CDP, NI, NH, HSSOC means.

2044


Q- What are the application in which PNP transistor is preferred over NPN ?

2843


What is the use of control cable?

686






How it the difference between force balance system and dispalacement balance system?

1603


What is Positive Calibration and Negative Calibration?

1766


draw shematic diagram of c/v positioner(smart type)?

1763


State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.

1547


the output of the common trasmitter protocol in qatar gas are the following

1562


How to Calibrate Flammable gas detector in field

722


Why thermo wells are used? What materials are used in thermo wells?

658


How an rtd work, and what volts/current goes to a rtd to measure the resistance?

734


The Design Calculation of Level Transmitter For Different Structure open & Closed Vessel, Eg. Diff. Level Tx., Capacitance For Continous Operation

2338


What is instrumentation control?

652