how to calculate temp.prapotional to mv in thermocoulpe.
Answer Posted / mohammad asfani
there is one formula with graphitical y=MX+b
for exma:Given a temperature transmitter with a measurement
range of -88 degrees to +145
degrees and a signal range of 4 to 20 milliamps, calculate
the proper signal output at an applied
temperature of +41 degrees.
Ans:take 41 deg and subtract to lrv mens -88. then 129 will
come and then you devide by span rang of transm..likespan
(145--88)=233,129/233=0.55 and take this number and
multiply by spanof current signal like 16ma and addto lrv
after that you can get ans...
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...
Galvanizing.
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?
Specific gravity.
can we replace a slot sensor (inductive type) with limit switch (potenial free contact / no-nc type).
If fire would be inside the plant which fire detector is to detected the fire.
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
applications of plc in printing and packaging?
How u measure the massflow in orifice flow measurement techniques
How to work togather like sov,limit switch,proxy switch and booster in xv
Derive capacitance to 4-20ma conversion formula / relation in capacitance type pressure sensor?
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
how to calibrate and troubleshooting of leveltroll?
how to calibrate corollaries (Mass flow meter)?