WHAT ARE THE DFT AND RMS MEASURMENTS PRINCIPLE IN NUMERICAL
TECHNOLOGY OF POWER SYSTEM ?? WHICH IS BETTER IN WHICH
QUANTITY MEASURNMENT??
Answer Posted / otto
RMS
The AC component is the effective mean value of the positive
and negative peak values.
RMS is used in applications where the effect of the DC
component must be taken
into account.
DFT
In the DFT mode, the fundamental frequency component of
the measured signal is numerically calculated from the
samples. In some applications, for example, it can be
difficult to accomplish sufficiently sensitive
settings and accurate operation of the low stage, which may
be due to a considerable amount of harmonics on the primary
side currents. In such a case, the operation can be based
solely on the fundamental frequency component of the
current. In addition, the DFT mode has slightly higher CT
requirements than the peakto-peak mode, if used with high
and instantaneous stages.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is center gravity load in substation?
how to wiring it with contactor and timer together
does any one know where we can purchase insulation oil for high voltage oil filled cables
WHAT HAPPENED DC SERIES MOTOR FIELD WINDING OPEN. CAN POSSIBLE.
WHAT IS MEANT BY OVER EXCITATION IN GENERATOR TRANSFORMERS? DESCRIBE IT.
how i chosse capacitor bank if my energy meter is 48 kvr? tell me capacitor bank chossen formula?
what is p.s impedance measurement test in earthing transformer?
Why power factor should not be in leading (capacitive) mode of any load.
How to work definite,over pluxing,revers power,OSR relay
Tell me all plants load factors i.e which plant operating on which load?
Difference between a pilot wire and a normal conductor?
what is interpose? where it is used and why it is used?
why does make gain margin and phase margin on same plot.?
What is T’Q and X’Q and X’D ? and what is saturated as well as unsaturated ?
can mini-curcuit supply MIL-tested transformer !