i have a dp tx range is 5000mmwc. in which calibration i use in a open tank.1.5*3.5*2.5 mtr.for level msmnt. what is the calculation.
Answer Posted / nitin sompura
See as per your data open tank height is 2.5 mtr
(2500mm).zero and 100% level if we consider as per your
tank and we suppose no safety margin for overflow as well
as for zero level for the pump, as you have not mentioned
clearly,
so according to you please keep your LP of DPT in
atmosphere, and HP point connect to the bottom of tank,and
if we consider tank of water then LRV:0.0mmWC,URL:2500 mmwc.
as per your medium you consider density.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
What is the diffrence between digital signal processing and discrete signal processing?
WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?
what is the calibration procedure for magnetic flow meter @ onsite
How do you identify an orifice in the pipeline?
key exchanges in wpa,wpa2,tls
What is the minimum rating availalbe for weld neck orifice in market?
is motorized valve closed when power shutoff?
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
What is the purpose of bypass valve across AS valve.
Hi Friends i need Electronics&Instrumentation Engg question papers for BARC written test by coming 20th May 2008 pls post ur use full info to kkumarei@gmail.com. Or for suggestions pls give one missed call to 9962122264
What is the PLC configuration in Cement industry?
why we us isolation barrier in hazardous area how it works to protect the area and please clarify its current flow.
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.
WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN
Which type of pressure can be measured by primary elements?