Answer Posted / a s nath
Local Breaker Backup (LBB) or Breaker Failure Pretection is
associated with Busbar Protection. If breaker fails to
operate due to its inoperable condition in spite of
operation of protective relays, there will be damage to the
system.This condition is being monitored by LBB relay or
BFR relay (Breaker Failure Relay)and will initiate the
Busbar protection and thus clears the bus.
The LBB protection will operate under the following
conditions:
(i) Lockout relay should operate
(ii)Current shall be more than 20% of normal current rating
(iii) The above currents shall persist after a time,
generally 200ms
When all the three conditions satisfy,it is considered that
the breaker is stuck and LBB protection will operate to
clear the bus.
By A S Nath
| Is This Answer Correct ? | 117 Yes | 8 No |
Post New Answer View All Answers
Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?
In parallel operation time both NGR’s close or not close if both close what will happen
Why is back emf used for a DC motor? Highlight its significance.
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
how we calculate torque ? how we improve it ?where torque will either motor or generator ?
how to determine the inrush current of a transformer
I HAVE A INCOMING 100A MCCB TPN 25KA, CABLE LENGHT OF 80M 70MM CABLE SIZE FROM MAIN SUBBOARD TO NEW DB.BASE ON THE FAULT LEVEL SETTING OF 45KA.I WOULD LIKE TO FIND OUT 25KA ENOUGH KA. APPRECIATE IF SOMEBODY CAN ASSIST ME WITH FORMULA FOR THIS. FRM: JEFF
WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.
Why neutral is not used in three phases dol starter
how to erect roof control panel?
Why earthing is necessary for any equipment?
A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N
How to select circuit breakers rating eg. if i select a circuit breakers of capacity 40 amps DC with operating voltage 28 volts and if i what to use same circuit breakers for 300 Volts DC application what is the current rating of this circuit breakers.
The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.
What is contract demand in solar system?