Why is it that bus reactors are not accompanied by a neutral
grounding reactor whereas a line shunt reactor is? PGCIL
does so.
Answer Posted / subbarayalu
In EHV Line, if there is single pole auto reclose used, during single phase fault, the faulty line may have arc current due to resonance which will disturb the auto reclose. Also, there will be transient recovery voltage. To compensate this effect we require Neutral Reactor in the EHV line. Whereas the same Auto Reclose condition will not be in Bus Reactor breaker. Hence, neutral grounding reactor is not required in Bus Reactor
| Is This Answer Correct ? | 16 Yes | 3 No |
Post New Answer View All Answers
why co incidence factor considered in transformer sizing?
What are unstable systems?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
what is mean by transition resistance of transformer?
If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??
what is difference between bus coupler and auto transfer switch
why we use sinosidal voltage / current instead of others in system?
if i get a drop in my 1st year and the i clear my 2nd year and 3rd year all clear and i dont have any back logs so can i be able to sit in campus selection??
What is miller crystal oscillator? Explain its operation?
What is the effect of pd controller on system performance?
why output is out of phase in case of common emitter?
why we use Test Terminal Block in 11 KV and 33 KV electrical panels.
What is an iron loss or core loss pi?
Explain about technical and non technical losses in distribution system?
11 kv input, 66 kv input advantages