If the primary side current of 33/11 transformer is 64 amps
then what will be secondary side current?
Answer Posted / technical1210
For a T/F
Vp/Vs=Is/Ip
so
33/11=3/1=Is/64
Is=64*3
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
How to design inductive load for 3 phase 440v and maximum 5 amps for star or delta? Can we use a 15kW, 1450rpm motor for 15kW, 960rpm apllication?If yes.how......n.if thesame motor used what`s it`s sideeefect.
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
Why the symbol of register is "zig zag"
hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.
How to Calculate Current Rating of SDFU (Switch Disconnector Fuse unit) for Protectionof Capacitor Bank connected to Busbar of 800Amp,in LV side of 11/0.433KV, 250KVA Transformer?
What is the difference between indoor and outdoor transformer
what is the difference between droop mode and ischnorous mode in thermal powerplant?
what is differentila pilot supervision in the incomer control panel in the power station?
How to test REF relay testing for LV panel as per Kahramaa standard?
Why an ac systems are preferred over dc systems?
how to synchronize 3 phase slip ring induction motors of different ratings.
How to decide and select the different earthing wire size for the different types of earthing
Why efficiency of generator is higher than motor at a particular load?
True or false question. 1.The fuse provide phase and neutral 2.power loss in electrical circuit can take place in (resistance or inductance or capacitance). 3.two phase system each phase has separated by a phase difference of (90 or 180 or 270 or 45). 4.3 phase balanced star connected load neutral current shall be (line current or phase current or zero or unity)
Different types of relay fault which phase sequence??