what is the difference between the 94 lockout relay and 86
lock out relay. I have noticed that the 94 lockout relay is
activated when the distance realy is activated and 86 is
activated when the 87T differential is activated. but why
can't the same lockouts be used for both the protection
schemes
Answer Posted / ayman elwardani
86 Lockout relays are used by many utilities in electrical
power transmission substations to trip and hold out of
equipment service within a protected zone on the occurrence
of protection relay operation which requires inspection
and/or repair before the zone may be safely placed back in
service. The original intent of lockout was that on
operation, maintenance or operating personnel would inspect
and repair as required the locked-out zone, and when clear,
would reset the lockout allowing operators to place the
element back in service. However in recent decades, it has
become normal to remotely control substations, resulting in
the absence of on-site personnel to reset a lockout in an
emergency situation
On the other hand, 94 inter-trip relay is used for up or
down stream backup protection to prevent the other side
breaker from supplying the faulty zone. The inter-trip
signal shall be cleared as the fault cleared and associated
relay has been reset.
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
How 48-relay (incomplete sequence) functions?
What do you mean by reach and reach the point of the relay?
what is the basic need of domestic loads 1- voltage 2- current
Draw the vector diagramme for Asynchronous Induction Generator at noload,half load and fullload.
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
How to design inductive load for 3 phase 440v and maximum 5 amps for star or delta? Can we use a 15kW, 1450rpm motor for 15kW, 960rpm apllication?If yes.how......n.if thesame motor used what`s it`s sideeefect.
specific difference of ICT&Auto Transformer
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
How to calculate flow of water delivered by pump when pressure & size of pipe line is given
difference between a diode and thyristor?
why do we have spikes enough to burn electronic boards, when generators are not grounded
Why i receive the GCU fault in my DG Sychronization panel . what all the factors considered for this fault .
what is Anti-pumping?
What is the previous name of Cox's Bazar
Plz tell me how we can find that particular company has vacancy or not