Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the problem in manufacturing transformer with 0
degree phase displacement.???why alwasys go for DYn11 or
DY5?Whys not DY0 i.e zero degree displacement between
primary and secondary side vectors?

Answer Posted / sujeet pandey

there can transformers with 0 degree or 180 degree phase
displacement like in the case of star-star or delta-delta .
In case of star-delta or delta-star transformer there is a
phase difference of +30 or -30 degree depending on
connection b/w them.This phase difference is due to the
relation b/w phase voltage of primary winding and phase
voltage of secondary winding.

Is This Answer Correct ?    18 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A 7 storey building has a floor area of 35,000sq.ft on each storey. On the ground floor 11KV electrical sub-station is to be erected. A load of 3kw for every 400sq.ft (p.f is 0.8) is proposed for each floor. fire pump 7.5hp, water pump 5hp, lift 2 nos, each 10hp and 20shop load of each shop is 5kw. calculate a. load each floor b. total load of building c. L.T feeders for aech floor and from transformer to main. d. distribution diagram e. capacity of sub-station/capacitor bank f. line diagram

2889


can i connect wavetrap in 2 different phase in EHV line?

1924


how give earthing conection to household equipment?

2094


Differentiate between ideal and non-ideal voltage sources?

1160


How to know Resistance and Reactance value of main and aux winding of single phase capacitor start capacitor run induction motor to find capacitor value?

2098


what are problems caused by the pdu in rack server

2038


Why DG set is not installed in Terrace ??

1285


Why does inductive loads consume KVARs?

2137


As per the Anchor capstan motor specification, full load current is 200A. starting current is 1750 A and acceleration time is less than 8 seconds. Please guide for selection of cable size.

1888


what do you mean by class PS CT and what are technical details needed for calculating it?

2054


Comment on the working principle of operation of a single-phase transformer.

1249


what is the difference b/w ATS and HTS?

2242


A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N

3059


please write motor, transformer, Generator setting, fault level calculation of Tr.etc

2108


How colour picturetube works & how many year it will works.

2100