On a 10 KVA UPS we have to provide a DC MCB for Battery bank
of 16 nos (12 V 65 AH).
What Shall be the current rating of DC MCB ?
Answer Posted / kathirvelan.j
Battery banks are always connected in series so the total
voltage of the battery bank will be
12*16=192V
10KVA=10000VA
A=10000/192=52 Amps
But we need to consider the safety margin of atleast 125%
on the MCB rating and also there are only standard current
ratings are only available in the market so by considering
all these reason we can go for a 65Amps DC MCB.
Is This Answer Correct ? | 16 Yes | 0 No |
Post New Answer View All Answers
How CFL &T5 tube light glows?
What is FTA card? How it works?
What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?
what reactive how to maintain
How to dimensioning SDCCH, LAPD and CS7 signaling on GSM?
In EDO ACBs what is a purpose of closing coil and motor, what is the operation of these devices are they inetconnected. means if we give supply to motor and by BCS we charge Closing coil,what exact is operation is and how it charge a spring of ACB. Sir if anybody has an wiring diagram please send me the link to operate and EDO breaker.
What do you understand by external characteristics of a d.c. Generator?
How does a tertiary winding filter harmonic(espcially 3rd one) from entering into load system?
Can any body tell me about INNER SHUNT COMPOUND MOTOR diagram?
What are the major reasons for balancing hydro-thermal mix?
what is the difference between electrical and electronic choke?
Explain M Var? Which types of problem occurs when reactive power increase at the time of full load of plant and at the time of synchronize of plant?
how we can set the IDMT relay.
What will be the effect if I use inverter as UPS mood?
HOW DOES THE ELECTRONIC ENERGY METER WORKS?