Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What are the starting currents of different motors and also
what are the running currents, and idle currents?

Answer Posted / dipak sonkusare

Stator winding resistance is very less and emf induced at
starting (E) = 0. As V=IR so I=V-E/R... i.e. Ist is very
high.

After (10min) starting and during running, E increases
gradually which decreses the running current (Ir).

Hence starting current is always more more (5-6times) the
rated / running current of motor.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we need to us lenz's law for synchornous motor

2624


In a tap changing transformer where is the tap connected, is it connected in the primary side or secondary side?

1186


why does the magnetic balance tests at transformer?

1996


What is the difference between Delta & Wye windings?

2136


what are the basic insulation levels & what its Unit

2067


How to measure the Harmonic Distortion of UPS ie THD?

2413


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2197


"TRANSFORMER MODELING AND ANALYSIS" MEANS WHAT AND WHICH TOPICS U READ IN THIS

1939


what is the formula for calculating the phase clerance between two phases and phase to earth how to calculate the cable for a motor

2098


What are the protections for safe running of electric generator?

2313


aternator every parts and its working

1675


What is mean by hot and cold loop testing? What is the difference between them?

1175


WRITEDOWN FEW RELY CODES

2319


what are the accessories need to be added while doing estimation for the following: 1.MCCB 2.MCB 3.ACB

2138


cc of scorpio?

2326