why we define potections of Tourbo generator in Class A & B.
Answer Posted / a.p.nanjappa
It is just the Client /owner/consultant choice.
As there are many protections in turbo alternater grouping
them in class A and B category indicate the severity of
faults and guess the extent of damages.
Class -A category need special attention and to be analized
cautiously.Ex- Generator differential means there is serous
trouble to identify the cause. Generator winding
damages,flash over..., It needs generator inspection and
tests. If it is ok then proceeds to Operations.
Where as Class -B an overload, overcurrent,under voltage...
secondary importance.Operational proceedure can be
followed.No need to trip units.However ,occurance of classB
protections also trips the turbo-alternator with time delay.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
If 24 KVA AVR having Input voltage 200-400v, Output voltage 415+-1%, what will be the voltage if Load is 13A.
WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME
what is the chemical name and formula of refrigarent R-134a.
In a large office how do we calculate required number of light fittings, assuming fittings are 4x18W or 2x36W fluorescent fitting ?
various transmission tower like .,D tower ,K.C.O tower ,C.C.O tower,K.C.R tower ,C.C.R tower ,H.C.O tower in different tons.
when generator short circuit condition, the current how dissipates. or at short circuit voltage not available then current how can flow?
What is the criteria for selecting the voltage classes of an AC Induction Motor.The KW rating above/below which ht/lt selection is made may be provided in details.
What is depreciation factor?
Why phase sequence must be same in any ht motor or generator circuit?if phase sequence doesn't same whatever will be affect on circuit?
With a phasor diagram show the effect of increasing the field current of a generator supplying a constant real power and connected to a grid system.
pre arcing time of ehv breaker
What are the components connected in between the power supply coming from an electric pole to HT & LT Panels in a large commercial building or how the power supply connected from Electric pole to Transformer & then to the HT & LT panels of a building? Please send me answers via mail, my id is yogiagarwal@gmail.com. If possible, please give a line diagram.
We have given to 3phase supply to ups system & how can coming netural
what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.
what happen if the load connected to the induction motor is taken away? the same question for synchoronous generator in synch i think that the the exitation voltage will appear on the terminal only if so plz answer me