Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why is starter necessary for a three-phase induction motor?

Answer Posted / subhakanta sahu

As we know at the time of starting an induction motor the rotor is stand still hence the slip is 1.if slip is 1 the rotor induced voltage is maximum hence drives maximum current in the rotor circuit.This rotor current current has impact on stator current(As per LENZ's law).This is the reason why an induction motor takes high current at starting(About 5 to 7 times the full load current).

This high current causes voltage fluctuation,unwanted power loss & unwanted stress to the system or equipment.So it has to be reduced by using different starting methods.

There are two possible ways to limit the starting current
1.Reduce the applied voltage.
2.Increase the rotor resistance.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

which type of stability limit is higher,steady state or transient? why?

1898


What happen to the transformer if the OLTC frequently used for lower and raise occured 50times daily?

2043


11 kV line deraction check by an Engineer.

1977


what will be the min and max voltage flow from neutral to earth?

1524


What is the differentional relay...what is the work of this in power Tx. how it is works..

1920


how to control the speed to switched reluctance motor

1944


Determine the BTU size of an aircon for 20 sq metre room

1874


i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.

1917


hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E

1975


hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.

1923


What do you mean by pull of electromagnet?

1034


1. transformer design formula ? 2. how to calculate the primary turns and secondry turns ? 3. core types ? 4. how to find the primary current and secondry current ? 5. how to calculate the stacking factor ? 6. range of fulx density ?

11181


How to calculate cable size in HT AND LT

2011


ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine

2096


why should small green grass ans small plant should not be there inside the transformer Yard in the factories

1750