Can I put my meter across an RTD to check it safely witout
tripping the equipment when it is connected to an
monitoring device eg.RTD module or IQ 1000
Answer Posted / s.k.bakshi
Yes you can do it.
1. force the analog input with such a value so that it is
beyond the tripping value.
2. Then open the leads and check the resistance of the rtd
in order to check wheather the rtd is faulty or not.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Where are oxygen analysers installed in cfbc boilers? What are their usual readings?
If fire would be inside the plant which fire detector is to detected the fire.
key phaser where is use and work
Why boiler chimney area oxyden sensor fixing?
i want formula for flow control.am doing project in flow control using orifice . i know value of the flow level(Q) . upstream(p1) pressure, orifice diameter(Do) , pipe diameter(Di) and oil viscosity(Vi) how can i calculate downstream pressure
we have level transmitter for h2s04 storage tank capacity 10k ,always there are failure of transmitter due to failure of magnetic floats ,please come up with solutions at the earliest.
How to decrease opening & closing time of on/off valve?
Draw symbols of the following :
any one can send me instrumentation previous interview papers? I prepare for MNC Company Interviews? my mail id- Rakesh.Golla@dodsaldxb.ae , and another mail rakesh.gvk@gmail.com
What is sensitivity in vibration probes..?
Explain why use mmwc unit?
What is solenoid valve? Where it is used?
what is piezoelectric transducer?give an example in power plant n state its principle?
what is moisture probe? What are there types? What is there working principle and how they works? guys this is one of technical question I had ask in interview. If you know its answer please let me know. The interviewers were more interested in microwave moisture probe, so if you find its any link please just forward me on my mail id.avinash1200@gmail.com Thanks in advance.
how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?