Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why NGR is required for 11Kv geneartor in power plant

Answer Posted / mahadeva annigeri

NGR USED IN 11KV GENERATING STATION IS TO LIMIT THE FAULT CURRENT WITHIN THE SPECIFIED LIMIT,Ex: AS PER FORMULA I=V/R,V=11KV.R=63OHM.SO 11000/1.732/63=100A,NGR WILL CONTROL UP TO 100A ONLY BECAUSE GENERATOR IS CONNECTED WITH GRID (SYNCHRONIZED CONDITION)HEAVY FAULT CURRENT MAY OCCURED IN LINE,THAT FAULT CURRENT MAY DAMAGE WINDING INSULATION THATISWHY NGR IS USED TO PROTECT THE GENERATOR FROM HEAVY FAULT CURRENT.I THINK SO

Is This Answer Correct ?    16 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is Control & Relay Panel? And Remote Control Center?

2226


if in 3-phase system voltage=440V,frequency=60Hz, current=400A. then if it is single phase then current=? and if it is single phasing then current=?

2565


How to calculate KVA/VA rating of PT or CT from primary & secondary voltage or primary & secondary current?

2433


Define settling time.

1177


How is efficiency of DG set calculated? At many places I found the efficiency to be mentioned in percentage. But at some other places I found kWH/ litres. I want to know how dimensionless percentage value is arrived at?

1926


if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.

1987


difference between power surge and switching transient

2099


how to find the torque of the single phase synchronous motor by doing an experiment

1945


what is reactive power?, why its measured in VA ? is it transient behavior of system?

2304


What are the commonly used schemes for the bus zone protection?

1067


An ELHNC 80amp 240v 30mA RCD is tripping periodically, every 30 - 180 seconds is it safe to disconnect the protection circuit?

2151


In a carnot engine with an efficiency of 40%, the heat rejected to the sink at 27 C is 60 kJ, then the heat supplied in kJ to the engine by the sources is

1082


what is the condition for YnD11

2563


What is meant by bus bar protection?

1190


grr resistance & contrator malt continuous

2162