Due to ferranti effect which power increases at the
receiving end?active power or reactive power?
Answer Posted / gk
There is no increase of reactive power as such because of
ferranti effect which happens under light load or no-load
situation. Suppose if there is no load, effect of line to
ground capacitance will come into picture. So receiving end
voltage Vr = Vs-(I*jXl)
= Vs-((-Vs/JXc)*JXl) assume I = Vs/(-JXc)
Vr=Vs(1+..)
therefore Vr > Vs under ferranti effect
Any additions or comments are welcome.TQ
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Which test will be more severe for VCB?
Why air circuit breaker off due to power failure?
in wind mill use 2100 kw asychronous generator ( induction generator ) rotor voltage : 3300,stator voltage : 690, rpm : 1511 type : MRL063E04 ' we check rotor resistance magger value found following. R-EARTH - 00 M.OHM,Y-EARTH-34 M.OHM,B-EARTH- 33M.OHM R-Y: 31 M.OHM, Y-B: 00 M.OHM,B-R :33 M.OHM HOW CAN I TAKE DECISION?pls ans. quickly
Why Transformer Neutral having one earth pit ( more earth electrode resistance) whereas body have many earth pit ( less earth electrode resistance)?
1 “earthing” for bonding of equipment and circuits to common plant earth electrode potential, 2 “protective earthing (PE)” when this bonding is required for personal safety provisions 3 “grounding” for interference suppressing bonding of screens, sys-tems with ground level 4. low-impedance earthing ? 5.primary earthing system and secondary earthing system what is that? 6.earthing electrode or mesh net earthing electrode ? very confusing , simple but very informative help required ? i will be very very thankful to you guys.
what is meant by vector group of a transformer? How can it be derived?
How it can worked plc based electrical system And which type of software using.
What is meant by vector group
WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.
What is the breaking capacity of transformer and how can we calculate the breaking capacity of tranformer
How can we design a HVAC Plant room which includes AHU,FCU,Chillers,Cooling towers, Pumps etc & how will they work? any Drawing if possible?
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
surge tank, hrc fuse, earthing transformer, firm power objective type
If a current -8+6sin6t is flowing three ammeter, one is a centre zero PMMC meter, one is true rms meter and one is moving iron meter. What are the reading of these three meter respectively?
BSNL TTA EXAM QUESTION