why we connect the capacitor bank in star , not in delta in
any system
Answer Posted / nishant2110
You are mistaken my friend,
Most of the time, we use DELTA capacitor bank in parallel to
the line to improve pf.
Actually
1. Delta connection provides 3 times more reactive power(kVAR)
than star.
2. less heat loss in delta
3. less triplen harmonic in delta
force to use delta over star capacitor bank.
Allthough, there are few instances where we use ungrounded
star connection but that is very rare.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
What is meant by derating factor?
what is difference between 9kv 5ka surge arrester and 9kv 10ka surge arrester.
What is Bolted fault?
What is meant by reactance voltage?
Between educational qualification and practical work experience, give us a brief explanation on your practical experience in your past Endeavour that you performed well to the satisfaction of your past or present employer?
Explain Circuit Breaker Trip Characteristics in detail.
what is the excess air in furnace
what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....
how much cable size required for 70 kilowatt load.
is the value of inductance depends upon the evalue of thitha in doubly excited machine?
we have a lot of model of rectifier but thyristor rectifier is the most rectifier that use in power system. Do you know why this rectifier is used?
Define the overload capacity of the motor?
explain all the classes with example
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
In convertor can we use rectifier thyristor in place of invertor thyristor with explain.