Answer Posted / aftab ahmed mazari
Differential pressure switch has two sensing ports. Hi and
Lo, Suppose set point of differential pressure switch is
30 PSI. Connect the pressure source at hi side of switch.
Leave Lo side (No any connection or any supply to low side)
Connect multimeter at switch terminals. Apply pressure at
high side. When pressure will reach 30 PSI, Switch will
operate and will change its contacts and also will be
indication at meter.
Suppose switch Low side is faulty, then apply 30 PSI at
High side and also apply low side pressure (5 to 10 PSI),
switch contacts should change, which indicate switch is
working.