Answer Posted / bhatt
As we know,capacity of conductor carrying conductor is
fixed in a perticular atmospheric conditions.Current in
transformer or DG set or alternators depends on load power
factor, current drawn by a perticular KW machine is more if
power factor is low whereas same KW rating machine wil draw
less current if it has high power factor.Hence
Transformer/DG/Alternator can not be designed for KW but
for KVA rating.It will feed high KW with high power factor
and low KW with low power factor without damaging winding
conductor/insulatin.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
in dc suppy frequency is zero why? if dc frequency is zero how to exist dc transients and ac transients
What are safety device in vcb and acb?
What is the function of auadag in a cro?
why in an industry; machine having rated 200 h.p stopped after power factor is maintained above 0.97 lag by control panel in view-of energy saving
How to design harmonic filter at the project stage without nowing the harmonics levels
what & how to check the lightning arrester
Shall I use 40A semiconductor Fuses in 32 A SFU ? Frame size is same. What Happen if Fuses burn on SFU?
how diside ct mf exmp.200/5 ct
how dia of wire and angles are calculated for overhead shielding wire to protect substation equipment from lightening strokes???
how many current required for hypo test
from which subjects most of the technical que will b asked for hpcl(electrical).pls help me
What will be the current if the resistance total in a series circuit doubles?
Why the standard of ambient teperature mentioned as 40 degree celcius in machines.
How does a transformer contribute towards the widespread popularity of ac system over dc?
a battery is having capacity 100AH and 25% charging .if a load taking 10A & connected 6 hour .what is the final condition of the battery.