Answer Posted / bhatt
As we know,capacity of conductor carrying conductor is
fixed in a perticular atmospheric conditions.Current in
transformer or DG set or alternators depends on load power
factor, current drawn by a perticular KW machine is more if
power factor is low whereas same KW rating machine wil draw
less current if it has high power factor.Hence
Transformer/DG/Alternator can not be designed for KW but
for KVA rating.It will feed high KW with high power factor
and low KW with low power factor without damaging winding
conductor/insulatin.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What are the parts in a inverter?
how can you calculate fault level ?
sent to a site and asked to explain how you would like a twenty seven flour building should be supplied with lighting and sockets plus a water boiler.
How test for Ddo vector group test condition?
what is the advantage of connecting capacitors in delta than in star?
what is RNG in the DG synchronizing by PLC?
anyone knows service engineer in chennai for EDM SPARKING MACHINE.CHMER PULSE CD 60 M.pL GIVE ANY CONTACT NOS
Both generator parallel condition shared load equally but one genrator taking ampere more than the other what are all the causes to make like this
What is the necessary and sufficient condition for stability.
how to remover corona effect and hysteresis losses from contactor
Pls mail me utility & Dg related question with answer
State the types of distortions in amplifier?
why should the primary of transformer be connected in delta in a heat run test?
Why armature rheostat is kept in maximum position?
I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?