generally transmitter power supply having some range(12v to
35v) but the out put(4-20 mA) must same for given input.If
we vary the power supply voltage then output mA also to be
change according to V=IR. Is there any voltage regulator
in the transmitter ?
Answer Posted / kyle condran
Transmitters act as a current source so the voltage drop across the Tx will change anyway in order to provide the correct current out. As long as the supplied voltage is in the range of the Tx, ie enough to power the unit and drive the signal, it will not affect the signal.
Ohms law get tricky when there is a "constant" current source in the loops
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
how pressurize drum calibrated ?
how to do dynolab wind speed sensor loop test, how to simulate value,i have simulate mA 4-20mA but not responding in DCS faceplate, please kindly advice me any one.
hi sir yhis is zahid ali i am preparing for the jspl at oct.4.please send me the recently updated sample paper.
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
Q-Explain the different load conditions that will produced different offset which may or may not be acceptable to thhe control function
can anyone tell me about the basic concepts to consider before to start a PLC panel wiring
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
what is zero and span ?
Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows
What is sensitivity in vibration probes..?
what do u mean by compensation n pid tunning?in pid tunning what you tunned?is it possible 2 tune p i d
What are different types of control valves?
What are the types of control valves available
what is exact time to study dcs and plc cources
How to calculate mmwc values into tonnes?